Helpful Advice: Glass
Toughened and Heatsoaked Balustrade Infill PanelsDesign Criteria / 4nr fixing bolts per panel /line load taken by the handrail
Horizontal uniformally
distributed line load KN/m |
Uniformally distributed
load applied to the infill KN/m2 |
A point load applied
to part of the infill KN |
Baluster centres |
Glass thickness mm |
0.36 |
0.5 |
0.25 |
<1.0 |
10 |
0.74 |
1 |
0.5 |
<1.0 |
10 |
1.5 |
1.5 |
1.5 |
<1.0 |
10 |
3 |
1.5 |
1.5 |
<1.0 |
10 |
0.36 |
0.5 |
0.25 |
1-1.25 |
10 |
0.74 |
1 |
0.5 |
1-1.25 |
10 |
1.5 |
1.5 |
1.5 |
1-1.25 |
10 |
3 |
1.5 |
1.5 |
1-1.25 |
10 |
0.36 |
0.5 |
0.25 |
1.25-1.5 |
10 |
0.74 |
1 |
0.5 |
1.25-1.5 |
10 |
1.5 |
1.5 |
1.5 |
1.25-1.5 |
10 |
3 |
1.5 |
1.5 |
1.25-1.5 |
10 |
0.36 |
0.5 |
0.25 |
1.5-1.8 |
10 |
0.74 |
1 |
0.5 |
1.5-1.8 |
10 |
1.5 |
1.5 |
1.5 |
1.5-1.8 |
12 |
3 |
1.5 |
1.5 |
1.5-1.8 |
12 |
0.36 |
0.5 |
0.25 |
2 |
10 |
0.74 |
1 |
0.5 |
2 |
12 |
1.5 |
1.5 |
1.5 |
2 |
15 |
3 |
1.5 |
1.5 |
2 |
15 |
Toughened and Heatsoaked Structural Glass Balustrade
Design Criteria
Horizontal uniformally distributed
line load KN/m |
Uniformally distributed load applied
to the infill KN/m2 |
A point load applied to part of
the infill KN |
Glass thickness mm |
0.36 |
0.5 |
0.25 |
12 |
0.74 |
1 |
0.5 |
15 |
1.5 |
1.5 |
1.5 |
19 |
3 |
1.5 |
1.5 |
25 |
It is recommended that the balustrade panels are heat soak tested. Loadings in accordance with: The Buildings Regulations 2000. Approved Document K.
B.S 6180:1999 Barriers In And About Buildings
B.S 6399 Part 1:1996 Loadings For Buildings
Code of Practice for dead and imposed loads
Prepared by Hubbard Architectural Metalwork Ltd and Solaglas. May 2006